The Issue Whether or not Respondents improperly serviced portable fire extinguishers and pre-engineered fire suppression systems as specifically alleged in the administrative complaints filed herein on October 8 and November 4, 1992.
Findings Of Fact During times material herein, Respondent Polk Fire Extinguisher Service, Inc. and its owner, Ira Devon Canady, was a licensed dealer for portable extinguishers and pre-engineered systems for fire protection and prevention. During times material hereto, Respondent Floyd E. Nicks, was a permittee for the servicing of portable extinguishers and pre-engineered systems. On or about January 29, 1992, Respondent Polk caused its licensed permittee, James G. Boykin, an employee under Respondent Polk's direct supervision and control, to service a pre-engineered fire suppression system at the Highway 27 truck stop in Lake Wales, Florida. On March 14, 1992, a fire started in the kitchen area of the truck stop. On March 17, 1992, Investigator Phillip J. Gruda, an employee in the fire sprinkler industry in excess of 26 years, was summoned to investigate the fire which occurred in the restaurant (kitchen area) of the truck stop wherein the fire suppression system failed to function as designed. Investigator Gruda immediately initiated his investigation. He noted that a fire started in the kitchen. The fire origin was in the area of the range hood which became completely engulfed in flames and the suppression system did not activate. The fire suppression system which was installed in the hood of the oven utilizes a fusible link which melts when exposed to intense heat. The melted link sets off an ignitor which lets the fire retardant powder from the system extinguish the fire. An examination of the system revealed that the control head was twisted and the cable which connects the fusible link and the remote pull station was twisted preventing the system from discharging. Investigator Gruda also discovered that the cable had dislodged from the pulley extending from the control head which further prevented the system from firing. On approximately January 29, 1992, Respondent Polk used its agent/permittee, Boykin, to also service two portable extinguishers at the truck stop in Lake Wales. Permittee Boykin failed to perform the required six-year maintenance on portable fire extinguisher No. 873430; failed to discover that the gauge on said extinguisher indicated it had discharged; failed to discover that the extinguisher had leaked and to remove the old label from the extinguisher; failed to perform the hydrostatic test on the extinguisher and placed an incorrect serial number on the service tag. Also, Boykin did not leak test the extinguisher. The above-referenced extinguisher failed to discharge during the fire on March 14, 1992 at the truck stop. On or about December 19, 1990, Respondent Polk caused its agent/permittee, Floyd E. Nicks, an employee under Respondent Polk's direct supervision and control, to service a pre-engineered system at the truck stop in Lake Wales. Respondent Nicks was dispatched to perform a six-year service maintenance on the system and at Respondent Polk's direction, used a generic BC powder instead of the required safety first specified powder thereby invalidating the underwriter's laboratory (UL) listing. During December, 1990, Respondent Nicks also failed to perform the required hydrostatic test for cylinder No. 24991 which was part of the pre- engineered system at the truck stop. Respondent, by its agent and employee Boykin, during December, 1991, serviced a pre-engineered system at the Lone Palm Country Club in Lakeland. Agent Boykin failed to properly service the system and investigations by Gruda subsequently revealed the following violations: S-4 Venturi was missing over the char- broiler appliance tee. Incorrect duct nozzles and plenum nozzles. Six elbows were used to connect the yoke instead of the specified five. The pipeline limits did not meet specifi- cation. The system was not piped in accordance with the manufacturer's instructions. The duct nozzle was not centered. The filters were not baffled and "range guard" corner pulleys were used instead of "safety first" as specified. Based on these violations, the gas charbroiler was not properly protected by the fire suppression system. On or about July 31, 1991, the parties entered a consent order against Respondent Polk wherein Respondent was placed on probation for one year. One condition of probation set forth in the Consent Order was that Respondent Polk would strictly adhere to all provisions of Chapter 633, Florida Statutes and rules and regulations promulgated thereunder.
Recommendation Based on the foregoing findings of facts and conclusions of law, it is RECOMMENDED that: Petitioner enter a final order revoking the licenses and permits of Respondents Polk Fire Extinguisher Service, Inc., Ira Devon Canady and Floyd E. Nicks. RECOMMENDED this 2nd day of August, 1993, in Tallahassee, Florida. JAMES E. BRADWELL Hearing Officer Division of Administrative Hearings The DeSoto Building 1230 Apalachee Parkway Tallahassee, Florida 32399-1550 (904) 488-9675 Filed with the Clerk of the Division of Administrative Hearings this 2nd day of August, 1993. APPENDIX TO THE RECOMMENDED ORDER IN CASE NO. 92-6551 and 92-0023 Ruling on Petitioner's proposed findings of fact. Paragraph 8, rejected as being a conclusion. COPIES FURNISHED: Tom Gallagher, State Treasurer and Insurance Commissioner Department of Insurance and Treasurer The Capitol, Plaza Level 11 Tallahassee, Florida 32399-0300 Bill O'Neill, General Counsel Department of Insurance and Treasurer The Capitol, Plaza Level Tallahassee, Florida 32399-0300 Daniel T. Gross, Esquire Division of Legal Services Department of Insurance and Treasurer 612 Larson Building Tallahassee, Florida 32399-0300 Ira Devon Canady, Owner Polk Fire Extinguisher Services, Inc. Post Office Box 384 Lakeland, Florida 33801 Floyd E. Nicks, pro se 1137 Carlton Lake Wales, Florida 33853
The Issue The issues to be resolved in this proceeding concern whether violations of Section 509.032, Florida Statutes, and Rule 61C-1.004(5), Florida Administrative Code, as well as Chapter 4A-3, Florida Administrative Code, had been committed by the Respondent in terms of two specific safety violations allegedly occurring at the Respondent's lodging establishment.
Findings Of Fact The Petitioner is an agency of the State of Florida charged, in pertinent part, with regulating the operation of hotel or lodging establishments in accordance with Section 20.165, Florida Statutes, and Chapter 509, Florida Statutes. The Respondent, at all times material hereto, has been licensed or otherwise subject to the Petitioner's jurisdiction. On September 28, 2001, and again on October 16, 2001, an inspector of the Division of Hotels and Restaurants (Division) inspected the Respondent's lodging premises. The Division inspector noted certain deficiencies at her first inspection and that those deficiencies where still outstanding and uncorrected at the end of her second inspection at that location. In light of the deficiencies noted at both inspections, the Division issued its Administrative Complaint on November 16, 2001, alleging that the fire extinguisher near Apartment Number One was in the "re-charge zone," meaning that it was inoperable on September 28, 2001, and was missing on October 16, 2001. The Complaint also charged that the balcony railing near Apartment Number Four was loose and, therefore, in an unsafe condition in violation of Rule 61C-1.004(5) and (6), Florida Administrative Code. In response, the Respondent testified that he does not live on the premises and that, although the fire extinguisher deficiency has occurred repeatedly, it is because children who are present on the premises keep discharging it. He testified that whenever it has been discharged he, or his maintenance man, immediately has it recharged by the Daytona Fire and Safety Company. Mr. Rampersad also testified that he did everything in his power to bring the railing up to proper code requirements by re-drilling holes and re-anchoring the railing in concrete. He contends that an "inspection supervisor" observed the railing and opined that it had been brought up to code, but there is no direct evidence of that observation. He established that, as of the time of the hearing, all necessary repairs to the railing had been made and that the fire extinguisher was charged and fully operable. He testified that at the time the fire extinguisher was missing upon the re-inspection date, found above, that it was at the service company being recharged.
Recommendation Having considered the foregoing Findings of Fact, Conclusions of Law, the evidence of record, the candor and demeanor of the witnesses, and the pleadings and arguments of the parties, it is, therefore, RECOMMENDED: That a final order be entered by the Department of Business and Professional Regulation, imposing a fine in the amount of $750.00; That the Respondent's license be suspended for six months, but with the suspension held in abeyance contingent upon timely payment of the administrative fine being received upon a schedule agreed to between the Respondent and the Director of the Division of Hotels and Restaurants. The failure to continue to make timely payments of the fine amount should result in imposition of the suspension of the Respondent's license; and That the Respondent be required to attend a Hospitality Education Program class under the auspices of the Petitioner within 60 days of the date of the final order herein and to provide satisfactory proof thereof to the Division of Hotels and Restaurants. DONE AND ENTERED this 8th day of January, 2003, in Tallahassee, Leon County, Florida. P. MICHAEL RUFF Administrative Law Judge Division of Administrative Hearings The DeSoto Building 1230 Apalachee Parkway Tallahassee, Florida 32399-3060 (850) 488-9675 SUNCOM 278-9675 Fax Filing (850) 921-6847 www.doah.state.fl.us Filed with the Clerk of the Division of Administrative Hearings this 8th day of January, 2003. COPIES FURNISHED: Milton Rampersad 1201 Kennedy Road, Apartment 19 Daytona Beach, Florida 32117 Charles F. Tunnicliff, Esquire Department of Business and Professional Regulation 1940 North Monroe Street Tallahassee, Florida 32399-2202 Geoff Luebkemann, Director Division of Hotels and Restaurants Department of Business and Professional Regulation 1940 North Monroe Street Tallahassee, Florida 32399-2202 Hardy L. Roberts, III, General Counsel Department of Business and Professional Regulation 1940 North Monroe Street Tallahassee, Florida 32399-2202
Findings Of Fact Official recognition is taken of the contents of the file in DOAH case number 86-3477 and the following facts from that file: On July 31, 1986, the Respondent denied the renewal of the Petitioner's license for an adult congregate living facility at the Clinton Crest Retirement Hotel, and advised him of his right to a formal administrative hearing as to relicensure. On August 8, 1986, the Respondent amended its basis for the proposed denial of licensure, alleging that on April 11, 1986, May 14, 1986, and July 18, 1986, Petitioner did not have a fixed fire extinguisher at the cooking appliance, did not have a three compartment sink or other approved system in use for the purpose of proper sanitation of kitchen utensils, and did not have a week's supply of non-perishable food based upon the number of weekly meals the facility had contracted to serve, and alleging that these were violations of specified statutes and rules. It further alleged that the fire extinguisher and the three compartment sink had remained uncorrected since June 20, 1985. The amended notice of proposed agency action cited the following provisions as the basis for the fire extinguisher requirement: sections 400.414 and 400.441, Fla. Stat., rules 10A-5.23(15)(a) and 4A-40.05, Fla. Admin. Code, and NFPA (National Fire Protection Association) 101, section 7-7.3 and NFPA 96. On August 11, 1986, the Petitioner requested a formal administrative hearing to contest the proposed denial of licensure. One year later, on August 14, 1987, the Respondent granted a renewal of license to the Petitioner. The Petitioner filed a motion for summary final order based upon issuance of the license. No response was filed by the Respondent. The Hearing Officer entered an order to the Respondent to show cause and to require a response. The Respondent filed a voluntary dismissal. The Petitioner moved to strike the voluntary dismissal, noting that he had requested the hearing, and requested attorneys' fees. The Respondent's response characterized the voluntary dismissal as a motion to dismiss for mootness, agreeing that the license had been issued. The Hearing Officer entered a recommended order recommending dismissal due to mootness, and noting that a request for attorneys' fees pursuant to section 57.111, Fla. Stat. (1987) would result in a final order and thus must originate with a separate petition to the Division of Administrative Hearings. The Respondent entered a final order dismissing the Petitioner's request for hearing as moot. The Petitioner then filed the instant petition for attorneys' fees and costs with the Division of Administrative Hearings. On June 20, 1985, Petitioner's facility was inspected. Two of the three violations set forth in the amended basis for denial of relicensure of August 8, 1986, were cited in the inspection report on June 20, 1985, and were reported as having not been corrected in a reinspection on September 26, 1985. P. Ex. 5. Those were the fire extinguisher issue and the three compartment sink issue. In the June 20, 1985, inspection report, the Respondent classified the three compartment sink violation as a class III violation, and required the violation to be corrected at the end of two months. The Respondent classified the fire extinguisher violation also as a class III violation, and required it to be corrected in three months. R. Ex. 5. An earlier administrative complaint had been filed against the Petitioner's facility on January 2, 1986. One of the allegations in that complaint was failure to have a fixed fire extinguisher at the kitchen stove. The Department classified this violation in the administrative complaint as a class III violation. The Petitioner entered into a stipulation in that administrative action paying, in part, a fine for this allegation of a fire code violation, and agreeing that if the deficiency was not corrected in thirty days, the result would be further administrative action, which might include "revocation proceedings." The stipulation did not clearly provide that failure to correct the violation would result in revocation of the license. The stipulation became embodied in the final order of the Respondent on March 19, 1986. R. Ex., 6. On April 11, 1986, and on May 14, 1986, the facility was inspected. Among other citations, the facility was cited for not have enough nonperishables to feed the 7 persons then living at the facility for a week, for not having a three compartment sink, and for not having a fire extinguisher over the cooking appliance. All three were classified as class III violations. R. Ex. 8. On reinspection on July 18, 1986, these items were still not corrected. In DOAH case number 86-3477, the Respondent admitted to requests for admissions that the three compartment sink issue and the non-perishable food issue were corrected by the date of the request for admissions, November 26, 1986. Thus, when that case closed, the only pending issue was the fire extinguisher over the stove. Based upon the testimony of James F. Schroeder, the Respondent's expert witness with respect to fire safety, the denial of relicensure in the letter of August 8, 1986, was primarily based upon the issue of fire extinguisher over the stove. The Petitioner's kitchen is small, approximately 6 to 8 feet in width and 10 to 12 feet in length. The stove is a residential electric stave having four burners. By design and construction, it is a domestic stove rather than what typically is thought of as a "commercial" stove. The stove is used commercially to prepare meals for residents of the adult congregate living facility for a fee. The stove is not located below a normal ceiling parallel with the floor, but is located under a lower slanted ceiling. The ceiling is only 4 to 6 feet above the front of the stove, and slants to within a few feet of the back of the stove. The ceiling is combustible, and a fire in the ceiling would spread to the rest of the adult congregate living facility unless extinguished by the automatic sprinkler system. The stove is near a window which could feed a stove fire with oxygen. The building is a wood frame building, and is highly susceptible to fire. There was a portable fire extinguisher at the stove. Additionally, the Petitioner installed fire sprinklers throughout the building at a cost of over $4,000. The automatic fire sprinklers were installed by the Petitioner to comply with the stipulated settlement dated March 19, 1986, and were installed after May 20, 1986. P. Ex. 3. The Petitioner thought he had been told by the Respondent that by installing the fire sprinkler system, he would satisfy the requirement that the stove have an automatic fire extinguisher. The fire sprinkler system that is installed included one in the kitchen, but the sprinkler in the kitchen is not located over the stove. R. Ex. 2. The kitchen fire sprinkler, which may be effective to impede a general fire in the kitchen, is not effective to smother a stove fire at the stove. Moreover, the one automatic sprinkler in the kitchen ceiling is not the same as an extinguisher at the stove because the stove fire extinguisher must have a manual operation capability as well as automatic capability, and must operate to shut off current to the stove in the event of fire. The lack of a fire extinguisher and hood at the stove poses a potential threat to the physical safety of the residents at the Petitioner's facility. The expert testimony presented was not sufficient to conclude as a matter of fact that the lack of a fire extinguisher and hood at the stove presents an imminent danger to residents or a substantial probability that death or serious physical injury would result there from, or that the lack of this equipment is a direct threat to the physical safety of the residents. The expert testimony was consistent with the classification by the Respondent of this violation as a class III violation. Petitioner's facility is licensed for 14 residents. On May 15, 1986, the Petitioner wrote to the Respondent asking that his license be reduced to 12 when it was reissued so that he would have time to obtain a three compartment sink. The Petitioner was having difficulty locating such a sink to purchase. The Petitioner intended to apply for a license for 14 residents when he had installed the sink. The Petitioner made this offer to the Respondent again in his letter of August 6, 1986, P. Ex. 4, and a letter from his attorney, P. Ex. 5, dated September 26, 1986. It was stipulated by the parties that rules 4A-40.05 and 4A-40.10, as embodied in R. Ex. 3, were applicable to the Petitioner on August 8, 1986. Conclusions of law 14 through 17 concern the contents of certain rules and provisions of the National Fire Protection Association (NFPA) standards, and are adopted as findings of fact. The Petitioner is the sole proprietor of the unincorporated business known as the Clinton Crest Retirement Hotel, which is the licensee in this case. The Petitioner is and was domiciled in the State of Florida, his principal office is and was in the State of Florida, he has not employed more than 25 full-time employees, and his net worth is not more than $2 million, including both personal and business investments. If attorneys' fees and costs are to be awarded in this proceeding, the unrebutted evidence justifies an award of $4,697.75 as reasonable attorneys' fees and $62.50 as reasonable costs.
The Issue Did the Respondent commit the offenses alleged in the Administrative Complaint Following Emergency Closure and, if so, what penalty should be imposed?
Findings Of Fact Upon consideration of the oral and documentary evidence adduced at the hearing, the following relevant findings of fact are made: The Department is the agency of the State of Florida charged with the responsibility of licensing and regulating public lodging establishments. At all times pertinent to this proceeding, Respondent was a licensed public lodging establishment as that term is defined in Section 509.013(4)(a), Florida Statutes, license number 38-00194-H, located at 1720 US Highway 27, Avon Park, Florida. At all times pertinent to this proceeding, Richard Barnhart was employed by the Department as a Sanitation and Safety Specialist. At all times pertinent to this proceeding, Ed Madden was employed by the Department as a Sanitation and Safety Supervisor. On March 10, 2000, Barnhart performed a routine inspection of Respondent's public lodging establishment (Litto's Apartments) and observed two safety violations which were classified as violations of critical concern. A violation classified as of critical concern is required to be corrected immediately. The safety violations observed by Barnhart were: (a) fire extinguisher missing on north side of Units 1 an 2 which resulted in some of the apartments located in Units 1 and 2 not having a fire extinguisher available within a maximum distance of 75 feet; and (b) no smoke detectors in apartments 1, 3, and 8. On March 10, 2000, Barnhart prepared a Lodging Inspection Report advising Respondent of, among other things, the safety violations that had to be corrected by March 18, 2000. Eugene Riggs, Respondent's Apartment Manager, acknowledged receipt of the inspection report listing the violations and the date for correction of the violations of critical concern. On March 21, 2000, Barnhart performed a Call Back/Re- Inspection of Litto's Apartments and observed the same safety violations that were observed on March 10, 2000. On March 21, 2000, Barnhart prepared a Call Back/Re- Inspection Report advising Respondent that the violations observed on March 10, 2000, had not been corrected. This report advised Respondent that the report should be considered a warning and that Respondent would be issued a Notice to Show Cause why sanctions should not be assessed against Respondent's license. Eugene Riggs acknowledged receipt of a copy of the Call Back/Re-Inspection Report. During a routine inspection conducted on March 21, 2000, Barnhart observed that: (a) the apartments' water supply was less than 75 feet from a septic tank and drain field, a sanitation violation of critical concern not observed on March 10, 2000; (b) there was raw sewage in an open septic tank on the premises, a sanitation violation of critical concern not observed on March 10, 2000; and (c) a septic tank had been disconnected resulting in raw sewage being dumped on the ground, a sanitation violation of critical concern not observed on March 10, 2000. Barnhart prepared a Lodging Inspection Report listing the violations observed during his routine inspection on March 21, 2000. Eugene Riggs acknowledged receipt of a copy of this report which, among other things, advised Respondent of the deadline of March 28, 2000, for correcting the additional violations observed on March 21, 2000, and the deadline of March 21, 2000, for correcting the violation observed on March 10, 2000, and not corrected by March 21, 2000. On March 28, 2000, Barnhart performed a Call Back/Re-Inspection of Litto's Apartments and observed that the violations observed on March 10, 2000, and March 21, 2000, had not been corrected. Barnhart prepared a Call Back/Re- Inspection Report on March 28, 2000, advising Respondent that the violations had not been corrected and that a Notice to Show Cause why sanctions should not be assessed against Respondent's license would be issued. On April 7, 2000, Barnhart and Supervisor Madden conducted a joint routine inspection of Litto's Apartments and observed that the violations of March 10, 2000, March 21, 2000, and March 28, 2000, had not been corrected. On April 7, 2000, a Lodging inspection Report was prepared advising Respondent that the violations noted on March 10, 2000, March 21, 2000, and March 28, 2000, had not been corrected. Based on the testimony of Richard Barnhart and Ed Madden, whose testimonies I find to be credible, there is sufficient evidence to show that: (a) a fire extinguisher was missing from the north side of the Units 1 and 2 which resulted in some of the apartments in Units 1 an 2 not having a fire extinguisher available within a maximum distance of 75 feet at the time of the inspection on March 10, 2000, and no fire extinguisher had been installed on the north side of Units 1 and 2 at time of the inspection on April 7, 2000, or during the intervening time; (b) smoke detectors were not installed in apartments 1, 3, and 8 at the time of the inspections on March 10, 2000, and smoke detector had not been installed in apartments 1, 3, and 8 at the time of the inspection on April 7, 2000, or during the intervening time; (c) at the time of the March 21, 2000, inspection, there was raw sewage in an open septic tank and sewage on the ground due to a septic tank blowout which had not been corrected at the time of the inspection on April 7, 2000, or during the intervening time; and (d) the water supply was located less than 75 feet from septic tank and drain field at the time of the inspection on March 21, 2000, which had not been corrected at the time of the inspection on April 7, 2000, or during the intervening time. Respondent's failure to have sufficient fire extinguishers properly located on its premises and Respondent's failure to correct this violation resulted in a significant threat to the public safety and welfare in that the residents were not properly protected from the danger of fire. Respondent's failure to provide smoke detectors in all of the apartments resulted in a significant threat to the public safety and welfare in that the residents were not being properly protected from the danger of fire. Respondent's failure to correct the contaminated water supply, correct the situation concerning the raw sewage being dumped on the ground, and to correct the situation where raw sewage was being left in an open septic tank resulted in a significant threat to the public health, safety, and welfare in that not only were the tenants being subjected to those unsanitary conditions but the general public as well. An Order of Emergency Suspension of License and Closure was issued by Respondent and signed by Gary Tillman, District Administrator, having been delegated this authority by the Director of Hotels and Restaurants. The Order of Emergency Suspension of License and Closure is dated March 7, 2000. However, this appears to be scrivener's error in that the order alleges violation that are alleged to have occurred on March 10, 21, 28, 2000, and April 7, 2000. Also, the Certificate of Service is dated April 7, 2000. The Order of Emergency Suspension of License and Closure was still in effect on December 18, 2000, the date of the hearing.
Recommendation Having considered the serious nature of the offenses committed by the Respondent, that Respondent is presently under an Order of Emergency Suspension of License and Closure for these same offenses, and that the Department is requesting that only an administrative fine be imposed against Respondent, it is recommended that the Department enter a final order finding that Respondent committed the offenses alleged in the Administrative Complaint Following Emergency Closure and imposing an administrative fine of $1,200.00 as requested by the Department. DONE AND ENTERED this 15th of February, 2001, in Tallahassee, Leon County, Florida. ___________________________________ WILLIAM R. CAVE Administrative Law Judge Division of Administrative Hearings The DeSoto Building 1230 Apalachee Parkway Tallahassee, Florida 32399-3060 (850) 488-9675 SUNCOM 278-9675 Fax Filing (850) 921-6947 www.doah.state.fl.us Filed with the Clerk of the Division of Administrative Hearings this 15th day of February, 2001. COPIES FURNISHED: Charles F. Tunnicliff, Esquire Division of Hotels and Restaurant Department of Business and Professional Regulation 1940 North Monroe Street Tallahassee, Florida 32399-0792 Litto's Apartments 1720 U.S. Highway 27 Avon Park, Florida 33825-9589 Ahmed Anjuman 1720 U.S. Highway 27 Avon Park, Florida 32825-9589 Susan R. McKinney, Director Division of Hotels and Restaurants Department of Business and Professional Regulation Northwood Centre 1940 North Monroe Street Tallahassee, Florida 32399-0792 Barbara D. Auger, General Counsel Department of Business and Professional Regulation Northwood Centre 1940 North Monroe Street Tallahassee, Florida 32399-0792
Findings Of Fact On November 16, 1981, Arnold J. Pergament, an inspector in petitioner's employ, visited Mr. Griffin's establishment. He found one fire extinguisher missing; one fire extinguisher to be of an unapproved type; and one that had last been serviced more than a year earlier. Mr. Pergament had originally called the fire extinguishers to Mr. Griffin's attention on July 20, 1981. Some structural wood had rotted, Mr. Pergament noted on November 16, 1981. Metal railings had wide spaces between vertical and horizontal members. These railings had been in place for approximately 15 years, however, without comment by Mr. Pergament who inspected all that time. On July 20, 1981, Mr. Pergament first noticed that a concrete walkway was in disrepair. In places, it was pitched at angles that made walking awkward. This situation persisted through November 16, 1981, even though it had originally been brought to Mr. Griffin's attention in July. By December 9, 1981, Mr. Griffin had begun taking steps to correct the deficiencies Mr. Pergament had listed. The parties stipulated that all problems had been corrected as of December 31, 1981.
Recommendation Upon consideration of the foregoing, it is RECOMMENDED: That petitioner fine respondent Twenty-five Dollars ($25). DONE AND ENTERED this 6th day of April, 1982, in Tallahassee, Florida. ROBERT T. BENTON, II Hearing Officer Division of Administrative Hearings The Oakland Building 2009 Apalachee Parkway Tallahassee, Florida 32301 (904) 488-9675 Filed with the Clerk of the Division of Administrative Hearings this 6th day of April, 1982. COPIES FURNISHED: L. E. Griffen Carlton Court Nine Northwest Avenue D Belle Glade, Florida 33430 John A. Boggs, Esquire Department of Business Regulation 725 South Bronough Street Tallahassee, Florida 32301 Sherman S. Winn, Director Division of Hotels and Restaurants 725 South Bronough Street Tallahassee, Florida 32301 ================================================================= AGENCY FINAL ORDER ================================================================= STATE OF FLORIDA DEPARTMENT OF BUSINESS REGULATION DIVISION OF HOTELS AND RESTAURANTS DIVISION OF HOTELS AND RESTAURANTS, Petitioner, vs. DOAH CASE NO. 82-298 H&R Control No. 60-2500H E. GRIFFIN d/b/a CARLTON COURT, Respondent. /
The Issue The issue in this case is whether Respondents illegally or improperly conducted testing of backflow prevention devices on fire line assemblies, and, if so, whether Petitioner should issue a Cease and Desist Order.
Findings Of Fact The Department, through its chief financial officer, who also acts as the state fire marshall, is the state agency responsible for, inter alia, the certification, licensing and monitoring of persons who engage in the business of layout, fabrication, installations, inspection, alteration, repair, or service of fire protection systems (other than pre-engineered systems). Respondents2 are licensed by the Florida Department of Business and Professional Regulation ("DBPR") as a certified plumbing contractor, License No. CFC054896-00012. Respondents are not certified by the Department to engage in the business of layout, fabrication, installations, inspection, alteration, repair, or service of fire protection systems (other than pre- engineered systems). As of the date of the final hearing, Respondents had not filed an application to be so certified. On or about June 29, 2006, Respondents conducted the annual Backflow Prevention Assembly Test inspection and maintenance on a backflow prevention device installed on a fire sprinkler fire line located at the University Park Country Club Clubhouse, 7651 and 7671 The Park Boulevard, University Park, Florida. The University Park Country Club Clubhouse is located within the Southern Manatee Fire and Rescue District. After performing the test at the University Park Country Club, Respondents issued a Backflow Prevention Assembly Test and Maintenance Report, and a copy was sent to the Manatee County Cross Connection Control Coordinator. At the conclusion of the test, Respondents determined the backflow device to be operating appropriately and placed an inspection tag on the device. On or about September 4, 2006, Respondents conducted the annual test on a backflow prevention device installed on a fire sprinkler fire line located at the Chiquita Banana Warehouse, 4610 18th Street East, Bradenton, Florida 34203. The warehouse is also located within the Southern Manatee Fire Rescue District. After performing the test, Respondents issued a Backflow Prevention Assembly Test and Maintenance Report. This report was also forwarded to the Manatee County Cross Connection Control coordinator. Respondents also placed an inspection tag on the backflow prevention device. On or about September 4, 2006, Respondents conducted the annual Backflow Prevention Assembly Test inspection and maintenance on a device located at the Manatee County Rural Health Services Treatment Center, 1515 26th Avenue East, Bradenton, Florida 34208. This center is also located within the Southern Manatee Fire Rescue District. Upon completion of the test, Respondents placed an inspection tag on the device and forwarded a Backflow Prevention Assembly Test and Maintenance Report to the Manatee County Cross Connection Control coordinator. On or about September 6, 2006, Respondents conducted the annual test on a backflow prevention device located at Sam's Warehouse Club, 5300 30th Street East, Bradenton, Florida 34203. The Sam's Warehouse Club is also located within the Southern Manatee Fire Rescue District. Upon completion of the test at Sam's Warehouse Club, Respondents placed an inspection tag on the device and forwarded a Backflow Prevention Assembly Test and Maintenance Report to the Manatee County Cross Connection Control coordinator. The backflow prevention devices inspected by Respondents are tied into domestic water lines which provide water to the surrounding community. It is imperative to keep the domestic water as clean and pure as possible. Backflow prevention devices serve the purpose of keeping contaminated or unclean water from re-entering the domestic water lines. It is extremely important that all backflow prevention devices be inspected and maintained on a regular basis. Testing of backflow prevention devices on designated fire lines (i.e., those lines connecting the domestic water line to a sprinkler system or other fire prevention system) is done by entities which have received a certification from the Department. The Department requires certified individuals to carry liability insurance coverage. The purpose of such coverage is to ensure that there will be money to correct any mistakes made by the certified inspectors. If a backflow system fails, the Department will immediately inspect to determine if the certified contractor made a mistake. If so, the contractor and his insurer will be required to pay for all damages and corrective action needed. The Department does not have any authority over plumbing contractors who have not been certified by the Department. Respondents routinely perform inspections and maintenance on backflow prevention devices. Respondents do not, in their own estimation, perform inspections on fire protection systems. Respondents maintain that fire protection systems start at a point just beyond the backflow prevention devices. Respondents are not certified by the Department to perform inspections and maintenance on fire protection systems. However, based on a letter from the Office of the Attorney General to Ruth Tirado, executive director of the Florida Association of Plumbing, Heating and Cooling Contractors, Respondents believe they are authorized to inspect backflow prevention devices that exist on a fire sprinkler line. The letter, dated February 3, 2004, states in pertinent part: Re: Your inquiry regarding back flow prevention presented to the Construction Industry Licensing Board at the meeting of January 15, 2004. * * * After review, and based upon the documentation presented, the Construction Industry Licensing Board has determined that back flow prevention is within the scope of work of a plumbing contractor. Please keep in mind that this opinion is based solely on the facts set forth in your letter and is not intended to be an opinion of general applicability. Furthermore, the Board has not conducted an independent factual investigation to determine whether other relevant facts do or may exist or whether the facts set forth in your letter may be governed by laws or rules other than Chapter 489, Part I, Florida Statutes and 61G4, Florida Administrative Code. It is clear the attorney general letter does seem to place backflow prevention within the "scope of work" of a plumbing contractor. However, there is no way to determine whether the opinion included any limitations, restrictions, or caveats, since the underlying letter it addresses was not placed into evidence. Nor is there any distinction in the letter concerning backflow prevention devices that are part of a fire sprinkler line. In October 2006, Henry Sheffield, deputy fire chief for the East Manatee Fire Rescue District, initiated a complaint against three plumbers relating to "fire line backflow preventers." A DBPR Uniform Complaint Form addressing one of the plumbers (a Mr. Jackson) indicates an alleged violation of Subsection 489.105(3), Florida Statutes. That statutory section deals with the scope of work for various kinds of contractors. A DBPR Uniform Complaint Form alleging violation of Section 633.021, Florida Statutes, is attached to the complaint form, but the DBPR Uniform Complaint Form does not indicate whether it relates to Mr. Jackson or one of the other plumbers. Also, admitted into evidence is a DBPR letter indicating dismissal of the complaint by one of the three plumbers (Mr. Wolf) relating to alleged violations of Chapter 489, Florida Statutes. The complaints against the three plumbers in 2006 may or may not be related to the same issues facing Respondents, but there is no way to connect them based upon the evidence presented at final hearing. The Department interprets Florida Administrative Code Rule 69A-46.040(2) to mean that the "point of service" for purposes of fire line backflow prevention to be the domestic water line where the fire line is tied in. That is, once there is a tie-in to the domestic water line, the Department has jurisdiction. This interpretation is reasonable and is based on the Department's experience over a number of years. Respondents maintain that the point of service begins immediately after the backflow prevention device. Therefore, they believe any work done on the backflow prevention device can be performed by a licensed plumbing contractor whether they have Department certification or not. This interpretation is not supported by the evidence presented. Respondents did not intentionally violate any provision of Chapter 633, Florida Statutes. All work performed by Respondents was done under the apparent authority given them by a state agency, the Construction Industry Licensing Board.
Recommendation Based on the foregoing Findings of Fact and Conclusions of Law, it is RECOMMENDED that a final order be entered by Petitioner, Department of Financial Services, ordering Respondents, Backflow Division of Systems Groups, Inc., and Robert H. Richey, Sr., to cease and desist from performing inspections and maintenance of backflow prevention devices on fire protection systems until such time that Respondents obtain the required certification to do so. DONE AND ENTERED this 26th day of February, 2009, in Tallahassee, Leon County, Florida. R. BRUCE MCKIBBEN Administrative Law Judge Division of Administrative Hearings The DeSoto Building 1230 Apalachee Parkway Tallahassee, Florida 32399-3060 (850) 488-9675 Fax Filing (850) 921-6847 www.doah.state.fl.us Filed with the Clerk of the Division of Administrative Hearings this 26th day of February, 2009.